In a hospital, airflow is not comfort. It is containment.

Full NEBB-certified Testing, Adjusting & Balancing across a new-build hospital in Kelantan, Malaysia, covering ward, treatment, and outpatient areas, and verifying the pressure regimes that hold theatres positive and isolation rooms negative.

Healthcare Kelantan, Malaysia TAB NEBB-certified
Project snapshotSKUD
SectorHealthcare
LocationKelantan, Malaysia
ScopeWard, treatment, and outpatient areas
ServiceTesting, Adjusting & Balancing
StandardNEBB-certified TAB methodology
OutcomePressure regimes verified and documented
Scope at a glance

Balanced as a building, proven as containment.

Air + water
Full hospital scope, both sides, one balance
Room by room
Every pressure-critical space proven individually, not inferred
Both ways
Opposing pressure regimes verified in adjacent spaces
Before opening
Infection control evidenced before the first patient arrived
The brief

A new hospital that had to be safe before it was occupied.

A new-build hospital needed its full HVAC scope balanced and documented before opening.

In most buildings, balancing decides whether people are comfortable. In a hospital it decides which way the air moves between rooms, and therefore what moves with it. An operating theatre is held positive so that nothing drifts in from the corridor. An isolation room is held negative so that nothing drifts out. Get the number wrong and the room does the opposite of its job, quietly, with nobody in the building able to see it.

The challenge

A pressure cascade is a chain, not a list of rooms.

  • Opposing regimes in adjacent spaces. Theatres are held positive so nothing drifts in. Isolation rooms are held negative so nothing drifts out. Sterile supply holds a dual regime across its clean and dirty sides. All of it on one floor, off one system.
  • Pressure is a relationship, not a reading. Every room borrows its differential from the spaces around it, so a change made to satisfy one room moves the rooms next to it.
  • The values are tiny and the tolerance is tight. An isolation room differential is a fraction of what a door swing or a lift shaft can do to a corridor, so the balance has to be right and stable, not merely right once.
  • Scale, with the theatre suite, critical care, sterile supply, and isolation rooms all drawing on the same building and the same plant.
Our approach

NEBB-certified TAB, air balanced and pressure proven.

Skud mobilised its NEBB-certified TAB methodology across the hospital, working to documented procedures so every reading was traceable and defensible.

  • Air-side balancing across every air handling unit, terminal unit, and supply and exhaust outlet, measured against the design airflow for each serving area.
  • Water-side setting and verification across every balancing valve.
  • Dedicated exhaust and fresh air verification for each pressure-critical space, so every one was proven individually rather than inferred from the floor around it.
  • Independent readings throughout. Skud did not install, supply, or commission any of what it measured.
The outcome

Every pressure-critical space verified to its design regime.

The full air and water scope was balanced to NEBB tolerances and documented. The theatres were verified positive, the isolation rooms verified negative, and the sterile supply regime confirmed across its clean and dirty sides, each measured against the pressure specified for that space rather than as a whole-building assumption.

The hospital was handed over with a NEBB-format certified TAB report: an independent, third-party record that the infection control strategy on the drawings existed in the building, room by room, before the first patient arrived.

Worked to ▸ NEBB Procedural Standard for TAB ▸ ASHRAE 111 ▸ Project healthcare ventilation criteria