Service · NEBB-certified measurement

Data centre particle counts that prove your halls are clean enough to run.

Independent ISO 14644-1 particle count testing for data halls, server rooms, and comms rooms. We verify the air after construction cleaning and whenever the specification requires it, so cleanliness is proven to class, not assumed, before the racks rely on it.

Performed to ISO 14644-1 by a firm NEBB (National Environmental Balancing Bureau) certified in Cleanroom Performance Testing, so the same accredited particle-count discipline used in pharma cleanrooms verifies your data halls.

Particle readoutISO 14644-1 ▸ SKUD
Point
Airborne particles ≥0.5µm · data hall, at rest
1,180,000 /m³
CleanerISO Class 8Class 8 limit
≥0.5µm count1,180,000 /m³Pass
≥1.0µm count312,000 /m³Pass
≥5.0µm count9,400 /m³Pass
Class achievedISO 8Ref
Certified ▸ NEBB · Cleanroom Performance Testing
The service

What particle count testing actually verifies.

Particle counting is the measurement that proves the air in your data halls is clean to a defined ISO class, by counting what is actually in it, location by location.

Data centre air can look clean and still carry enough fine particulate to foul boards, clog heat sinks, and quietly erode cooling. After construction or a deep clean, the only way to know the room hit its target is to count it.

Skud's role is the independent measurement. We verify the result to ISO 14644-1 and certify it, and that third-party certificate is the proof a facilities lead, OEM, or auditor accepts. It also gives whoever carried out the cleaning a documented confirmation the work reached class.

Sample

Multiple particle-count readings per location, at the ISO sizes for the target class, with calibrated counters.

Classify

Compare measured counts against ISO 14644-1 limits to confirm the class, at rest and in operation.

Certify

Issue a classification certificate, a point-by-point report, and an action plan if anything falls short.

When data centres call us in

The two moments cleanliness has to be proven.

Particle count testing is how you prove a clean actually worked, before anything important depends on it.

Trigger 01

After construction cleaning

Once the builders' clean and specialist cleaning are done, we verify the halls actually reached class before IT equipment goes in or the room is energised. This is the cleanliness sign-off your handover depends on.

Trigger 02

After periodic or specialist cleaning

After specialist cleaning, remedial work, or at whatever interval your specification or equipment manufacturer sets, we re-verify cleanliness to class, so the work is proven to have reached the required standard and the environmental record stays current.

Either way

Independent certification

An independent third-party count gives the cleaning team, the contractor, and the owner one documented result everyone can stand behind. It is the proof that completes the handover pack, from a party with no stake in the cleaning it verifies.

What we measure

Focused measurements that reflect your real operating conditions.

Counts taken where contamination actually reaches the hardware, under the states that matter.

Counts

Airborne particle concentration

  • Counts at the ISO 14644-1 sizes for your class
  • ≥0.5, ≥1.0 and ≥5.0µm as required
  • Multiple readings per location for confidence
Coverage

Locations that matter

  • Supply diffusers & returns
  • Rack fronts, doorways & intake paths
  • Point count scales with room volume & risk
States

States of operation

  • At rest for a clean baseline
  • In operation for staff movement & load
  • Both states where required
Calibrated

Verification & calibration

  • On-site instrument verification
  • Counters calibrated to ISO 21501-4
  • Accuracy & repeatability you can defend
Standards & references ▸ ISO 14644-1:2015 ▸ ISO 21501-4 ▸ ASHRAE TC 9.9 datacom guidance
Typical ISO classes

The class your specification or equipment manufacturer requires.

Most data centres are specified to ISO Class 8, with tighter zones held to Class 7. We confirm the target with you before testing.

Target classReference limit at ≥0.5µmWhere it is used
ISO Class 83,520,000 particles / m³Most data halls and comms rooms
ISO Class 7352,000 particles / m³Higher-density or higher-risk zones
Cleaning just finished?

Verify the halls to class before the racks rely on it.

How we work

A simple four-step flow that ends in certification.

Every engagement runs the same way, so the result is traceable and the report stands up.

Scope & plan

Agree the target ISO class, rooms, sampling points, and states with your team, sized to room volume and risk.

Set up & verify

Airflow checks and on-site instrument verification before a single reading is logged.

Measure & classify

Capture particle counts at each point and compare against ISO 14644-1 limits to classify every area.

Report & certify

Issue the certificate, the full report, and a prioritised action plan with clear next steps.

What you receive

Documentation built for handover and audit.

Every figure measured, mapped, and built to be read, audited, and signed.

ISO 14644-1 classification certificate

A classification certificate for every tested area and state, issued to the ISO 14644-1 limits for your target class.

Full point-by-point report

Every reading mapped, with a pass or fail summary, a hot-spot map, and root-cause notes.

Prioritised action plan

Clear next steps across filtration, sealing, cleaning, and airflow wherever an area falls short.

Optional follow-up

Retest after remediation, plus periodic monitoring in line with ISO guidance.

Why it matters

Clean air protects uptime and hardware life.

Independent particle counting turns invisible risk into a number you can act on.

01 / Uptime

Protect the hardware

Reduce particulate fouling on boards and heat sinks, preserve cooling efficiency and airflow, and prevent contamination-driven faults before they cost you.

02 / Compliance

Specification and OEM aligned

Measured against the ISO class your project specification or equipment manufacturer requires, with an environmental record you can keep current and trend over time.

03 / Independence

Third-party certified

Performed with NEBB-certified Cleanroom Performance Testing methodology, our report gives every party one neutral and traceable set of results, including the cleaning team, who get documented proof the work reached class.

Where we test

Every space in the facility that has to stay clean.

Data halls
Server rooms
Comms & MMR rooms
Edge & micro data centres
Colocation & hyperscale
AHU & intake paths
Common questions

Data centre particle counting, answered plainly.

When should particle count testing be carried out?

Particle count testing should normally be completed after the final construction clean and before the data hall is handed over, populated or fully energised. This establishes a documented cleanliness baseline before sensitive IT equipment begins operating.

Retesting may also be required after major construction work, contamination incidents, changes to filtration, specialist cleaning or at intervals stated in the project specification, operating procedure or equipment manufacturer’s requirements. There is no universal rule requiring every data centre to be tested annually.

What ISO cleanliness class does a data centre need?

There is no single ISO class that automatically applies to every data centre. ISO 14644-1 provides the method for classifying air cleanliness by airborne particle concentration, while the required class must come from the project specification, owner’s requirements or IT equipment manufacturer.

ISO Class 8 is a common requirement for data halls and rack areas. IBM and NVIDIA are among the equipment manufacturers that specify ISO 14644-1 Class 8 conditions for applicable data centre environments. ISO Class 7 should only be applied where it is specifically required by the project or equipment criteria.

Why appoint an independent party for particle count testing?

Independent testing gives the owner, consultant, main contractor and cleaning contractor one neutral and traceable set of results.

Skud measures the airborne particle concentration against the agreed acceptance criteria and provides a formal report identifying the test locations, measured results and compliance status. This supports handover, quality verification and corrective action without relying solely on the party that performed the cleaning.

Independent testing supports project acceptance, but it should not be described as automatically protecting every OEM warranty or satisfying every insurer unless that requirement is confirmed in the relevant contract or warranty terms.

Should testing be carried out at rest or in operation?

The required test condition should be agreed before mobilisation.

At rest testing provides a controlled baseline after cleaning, with the environmental systems operating but without normal personnel activity.

In operation testing measures airborne particle conditions while the data centre is functioning under its defined operating conditions, including normal equipment and personnel activity.

ISO cleanroom test methods recognise as-built, at-rest and operational occupancy states, but the correct condition for a data centre depends on the project’s acceptance criteria and intended purpose of the test.

What happens if an area fails the required particle count?

The report will identify the failed sampling location, measured particle concentration and applicable acceptance limit. Where patterns are visible, the findings may indicate areas requiring further investigation, cleaning or inspection.

Possible contributors can include incomplete cleaning, unsealed openings, damaged or unsuitable filters, construction activity, personnel movement or contaminated airflow. However, particle counting alone does not always establish the exact root cause.

After corrective work is completed, Skud can retest the affected locations to verify whether the required cleanliness class has been achieved.

Get a proposal

Prove the clean. Close out the data hall.

Independent post-clean particle counting for data centres. We test against the agreed cleanliness requirements, document the results and issue a clear report for client or consultant sign-off. Send us the hall areas, testing specification and programme.

  • Independent evidence for client and consultant sign-offn
  • Night, weekend and phased testing to match your cleaning schedules
  • Failed areas clearly identified for targeted re-cleaning and retesting