After construction cleaning
Once the builders' clean and specialist cleaning are done, we verify the halls actually reached class before IT equipment goes in or the room is energised. This is the cleanliness sign-off your handover depends on.
Independent ISO 14644-1 particle count testing for data halls, server rooms, and comms rooms. We verify the air after construction cleaning and whenever the specification requires it, so cleanliness is proven to class, not assumed, before the racks rely on it.
Performed to ISO 14644-1 by a firm NEBB (National Environmental Balancing Bureau) certified in Cleanroom Performance Testing, so the same accredited particle-count discipline used in pharma cleanrooms verifies your data halls.
Particle counting is the measurement that proves the air in your data halls is clean to a defined ISO class, by counting what is actually in it, location by location.
Data centre air can look clean and still carry enough fine particulate to foul boards, clog heat sinks, and quietly erode cooling. After construction or a deep clean, the only way to know the room hit its target is to count it.
Skud's role is the independent measurement. We verify the result to ISO 14644-1 and certify it, and that third-party certificate is the proof a facilities lead, OEM, or auditor accepts. It also gives whoever carried out the cleaning a documented confirmation the work reached class.
Multiple particle-count readings per location, at the ISO sizes for the target class, with calibrated counters.
Compare measured counts against ISO 14644-1 limits to confirm the class, at rest and in operation.
Issue a classification certificate, a point-by-point report, and an action plan if anything falls short.
Particle count testing is how you prove a clean actually worked, before anything important depends on it.
Once the builders' clean and specialist cleaning are done, we verify the halls actually reached class before IT equipment goes in or the room is energised. This is the cleanliness sign-off your handover depends on.
After specialist cleaning, remedial work, or at whatever interval your specification or equipment manufacturer sets, we re-verify cleanliness to class, so the work is proven to have reached the required standard and the environmental record stays current.
An independent third-party count gives the cleaning team, the contractor, and the owner one documented result everyone can stand behind. It is the proof that completes the handover pack, from a party with no stake in the cleaning it verifies.
Counts taken where contamination actually reaches the hardware, under the states that matter.
Most data centres are specified to ISO Class 8, with tighter zones held to Class 7. We confirm the target with you before testing.
| Target class | Reference limit at ≥0.5µm | Where it is used |
|---|---|---|
| ISO Class 8 | 3,520,000 particles / m³ | Most data halls and comms rooms |
| ISO Class 7 | 352,000 particles / m³ | Higher-density or higher-risk zones |
Every engagement runs the same way, so the result is traceable and the report stands up.
Agree the target ISO class, rooms, sampling points, and states with your team, sized to room volume and risk.
Airflow checks and on-site instrument verification before a single reading is logged.
Capture particle counts at each point and compare against ISO 14644-1 limits to classify every area.
Issue the certificate, the full report, and a prioritised action plan with clear next steps.
Every figure measured, mapped, and built to be read, audited, and signed.
A classification certificate for every tested area and state, issued to the ISO 14644-1 limits for your target class.
Every reading mapped, with a pass or fail summary, a hot-spot map, and root-cause notes.
Clear next steps across filtration, sealing, cleaning, and airflow wherever an area falls short.
Retest after remediation, plus periodic monitoring in line with ISO guidance.
Independent particle counting turns invisible risk into a number you can act on.
Reduce particulate fouling on boards and heat sinks, preserve cooling efficiency and airflow, and prevent contamination-driven faults before they cost you.
Measured against the ISO class your project specification or equipment manufacturer requires, with an environmental record you can keep current and trend over time.
Performed with NEBB-certified Cleanroom Performance Testing methodology, our report gives every party one neutral and traceable set of results, including the cleaning team, who get documented proof the work reached class.
Real projects, anonymised to sector and location. Every detail comes straight from the verification report.
Particle count testing should normally be completed after the final construction clean and before the data hall is handed over, populated or fully energised. This establishes a documented cleanliness baseline before sensitive IT equipment begins operating.
Retesting may also be required after major construction work, contamination incidents, changes to filtration, specialist cleaning or at intervals stated in the project specification, operating procedure or equipment manufacturer’s requirements. There is no universal rule requiring every data centre to be tested annually.
There is no single ISO class that automatically applies to every data centre. ISO 14644-1 provides the method for classifying air cleanliness by airborne particle concentration, while the required class must come from the project specification, owner’s requirements or IT equipment manufacturer.
ISO Class 8 is a common requirement for data halls and rack areas. IBM and NVIDIA are among the equipment manufacturers that specify ISO 14644-1 Class 8 conditions for applicable data centre environments. ISO Class 7 should only be applied where it is specifically required by the project or equipment criteria.
Independent testing gives the owner, consultant, main contractor and cleaning contractor one neutral and traceable set of results.
Skud measures the airborne particle concentration against the agreed acceptance criteria and provides a formal report identifying the test locations, measured results and compliance status. This supports handover, quality verification and corrective action without relying solely on the party that performed the cleaning.
Independent testing supports project acceptance, but it should not be described as automatically protecting every OEM warranty or satisfying every insurer unless that requirement is confirmed in the relevant contract or warranty terms.
The required test condition should be agreed before mobilisation.
At rest testing provides a controlled baseline after cleaning, with the environmental systems operating but without normal personnel activity.
In operation testing measures airborne particle conditions while the data centre is functioning under its defined operating conditions, including normal equipment and personnel activity.
ISO cleanroom test methods recognise as-built, at-rest and operational occupancy states, but the correct condition for a data centre depends on the project’s acceptance criteria and intended purpose of the test.
The report will identify the failed sampling location, measured particle concentration and applicable acceptance limit. Where patterns are visible, the findings may indicate areas requiring further investigation, cleaning or inspection.
Possible contributors can include incomplete cleaning, unsealed openings, damaged or unsuitable filters, construction activity, personnel movement or contaminated airflow. However, particle counting alone does not always establish the exact root cause.
After corrective work is completed, Skud can retest the affected locations to verify whether the required cleanliness class has been achieved.
Independent post-clean particle counting for data centres. We test against the agreed cleanliness requirements, document the results and issue a clear report for client or consultant sign-off. Send us the hall areas, testing specification and programme.