Airflow measurement methods in HVAC, explained.
A TAB report is only as good as the measurements behind it, and airflow can be measured several ways. This guide sets out the three main methods, capture hood, anemometer traverse, and Pitot velocity-pressure traverse, and when each is the right one to use.
- Three main methods measure airflow: capture hood at terminals, anemometer traverse across faces, and Pitot velocity-pressure traverse inside ducts.
- The Pitot traverse is the reference method for ducted airflow because it samples the whole cross-section, distributed by the log-Tchebycheff rule.
- A capture hood is fastest at diffusers and grilles, provided it is back-pressure compensated so it does not distort its own reading.
- The biggest source of error is using the wrong method for the location, not the instrument. Every instrument must carry traceable calibration.
Every airflow figure in a TAB report comes from a choice of method, and the choice matters as much as the instrument. Measure a duct with the wrong technique, or a diffuser with an uncompensated hood, and you get a confident number that is quietly wrong. Knowing which method belongs where is the difference between a defensible reading and a plausible-looking guess.
There are three principal methods, each suited to a different point in the system.
Capture hood (flow hood)
A capture hood is placed over a diffuser, grille, or register to read the airflow passing through it directly. It is the fastest and most practical method at air terminals, which is why it is the workhorse of air-side balancing. The critical caveat is back-pressure: the hood adds a small resistance to the terminal, which can change the very airflow it is measuring, so a quality hood applies back-pressure compensation to correct for its own effect. An uncompensated hood reading is a common, and avoidable, source of error.
Anemometer traverse
An anemometer measures air velocity at a point, and by traversing it across the face of a grille, an open duct, or a filter, and averaging the readings, airflow is derived from velocity and area. Two types are common: rotating-vane anemometers, which suit larger open faces and higher velocities, and thermal (hot-wire) anemometers, which read low velocities well. The method depends on a representative set of traverse points; too few, or poorly distributed, and the average does not represent the true flow.
Pitot-tube velocity-pressure traverse
Inside a duct, airflow is measured with a Pitot tube, which reads velocity pressure at a point. By traversing across the duct cross-section at points distributed by a defined rule, the log-Tchebycheff method is preferred for accuracy, and converting velocity pressure to velocity, the average airflow is derived. This is the reference method for ducted airflow precisely because it samples the whole cross-section rather than trusting a single central reading, which the duct’s velocity profile would make unrepresentative.
| Method | Best for | Key caveat |
|---|---|---|
| Capture hood | Diffusers, grilles, registers | Must be back-pressure compensated |
| Anemometer traverse | Open faces, large grilles, filters | Needs representative traverse points |
| Pitot traverse | Ducted airflow (reference method) | Points set by log-Tchebycheff rule |
▸ The larger error is almost never the instrument. It is measuring the wrong way in the wrong place, and trusting the number anyway.
Why the method shows up in the report
A defensible TAB report does not just list airflow figures; it stands behind them with the method and the calibrated instrument used to take them. When a consultant questions a reading, the answer is the method and the calibration certificate, not “that is what the hood said.” This is why airflow measurement is inseparable from the wider discipline of reading an air balancing report, and why it sits at the core of testing, adjusting and balancing.
Frequently asked questions
How is airflow measured in HVAC?
What is a Pitot traverse?
What is a capture hood used for?
Which airflow measurement method is most accurate?