Cleanroom Performance Testing · The basics

Cleanroom HVAC systems: how they work and how they are tested.

What a cleanroom HVAC (ACMV) system does that comfort air conditioning never has to, how air changes, airflow patterns and pressure cascades hold a class, and the ISO 14644 tests that prove it.

By Skud Technical· 7 min read· Updated October 2026
The short version
  • Supply air passes through HEPA or ULPA filters before it enters the room.
  • The system supplies far more air than an office does, often 20 to 60 air changes an hour, or more in the cleanest rooms.
  • Rooms are held at different pressures so air flows from clean to less clean.
  • Testing checks each of these: filter integrity, airflow, pressure, particle count, recovery, temperature and humidity.

A cleanroom HVAC system does three jobs that comfort air conditioning never has to do: it filters the air to a particle limit, keeps air moving from clean areas to less clean ones, and holds temperature and humidity inside tight bands. In Malaysian specifications you will usually see it called the cleanroom ACMV system. It is the same thing.

The cleanroom only meets its ISO class if this system works. That is why most of a cleanroom test is really a test of the air system behind it.

How a cleanroom HVAC system works

Most cleanroom systems follow the same path: outside air is conditioned, mixed with return air, filtered twice, and delivered through terminal filters at the ceiling. The main parts are these.

  • Makeup air unit (MAU). Treats the fresh outside air. In Malaysia’s climate its biggest job is removing moisture before the air reaches the room.
  • Air handling unit (AHU). Mixes fresh and return air, cools or heats it, and pushes it through pre-filters and bag filters. Fan speed sets how much air the room gets.
  • Terminal HEPA or ULPA filters. The final filter, fitted in the ceiling as filter housings or fan filter units (FFUs). This is where particle control actually happens.
  • Return air path. Low-level wall returns, raised floors or return air chases carry air back to the AHU. Where the returns sit decides how air sweeps through the room.
  • Exhaust and pressure control. Exhaust fans, dampers and pressure controls keep each room at its setpoint as doors open and process equipment runs.
  • Controls and monitoring. A BMS or EMS tracks temperature, humidity and pressure, and raises alarms when they drift.

A weakness in any one part shows up in the room. A clogged pre-filter lowers airflow. A leaking HEPA seal lets particles past. A sticking damper upsets the pressure cascade.

Air changes, airflow patterns and pressure cascades

Three design choices decide whether a cleanroom can hold its class: how much clean air goes in, which way it moves, and how rooms are pressurised against each other.

Air change rate. ISO 14644 does not set a fixed air change rate. Designers choose one for the class, the process and the heat load. Rooms at ISO 7 and ISO 8 commonly run in the range of roughly 20 to 60 air changes an hour. More air dilutes particles faster, but it also costs more fan energy every hour the room runs.

Airflow pattern. There are two main types:

  • Non-unidirectional (turbulent) flow. Filtered air enters through ceiling filters, mixes with room air and leaves through low returns. It cleans by dilution. Most ISO 6 to ISO 8 rooms work this way.
  • Unidirectional (laminar) flow. Air moves in parallel streams at a steady speed, usually from a full HEPA ceiling down to a perforated floor or low returns. It sweeps particles away instead of diluting them. It is used for ISO 5 and cleaner zones. For pharmaceutical Grade A, EU GMP Annex 1 suggests a velocity range of 0.36 to 0.54 m/s.

Pressure cascade. Cleaner rooms are held at higher pressure than the rooms around them, so when a door opens, air flows outwards, not inwards. EU GMP Annex 1 gives a guidance value of at least 10 Pa between adjacent rooms of different grades. Containment suites, such as some biosafety and potent drug areas, reverse the logic and hold the room negative to keep material in.

Temperature and humidity control

The process sets the temperature and humidity limits, not the ISO class. A lithography bay, a tablet compression suite and a cell therapy lab can share an ISO class and still need very different conditions.

In Malaysia, humidity is usually the harder of the two. Outside air is hot and wet all year, so the makeup air unit has to cool air below its dew point to pull moisture out, then often reheat it to the supply temperature. If the coil is undersized or the chilled water supply runs warm, humidity creeps up first.

Why it matters:

  • High humidity can affect hygroscopic powders, promote microbial growth and cause condensation on cold surfaces.
  • Low humidity raises static, which attracts particles and can damage electronic components.
  • Unstable temperature affects dimensional accuracy in precision manufacturing and operator comfort in gowning.

How a cleanroom HVAC system is tested

Cleanroom testing follows ISO 14644. Part 1 sets the particle limits for each class. Part 3 describes the test methods for the systems behind them. Most of those tests check the HVAC system directly.

Cleanroom HVAC tests and what a failure points to
TestWhat it checksWhat a failure usually points to
Airflow volume or velocitySupply air per filter or per room, and air change rate. Velocity across the filter face for unidirectional zonesDirty pre-filters, fan speed, damper settings, filter loading
Installed filter leak testHEPA or ULPA filter media, gaskets and frames, scanned with an aerosol challengeDamaged media, poor seals, frame bypass
Pressure differencePressure between each room and its neighbours, against the design cascadeExhaust or supply imbalance, door leakage, control setpoints
Airflow direction and visualisationSmoke studies showing how air moves around equipment, doors and work zonesDead spots, reverse flow, turbulence over critical work
Airborne particle countParticle concentration at set locations against the ISO class limitAny of the above, or room occupancy and cleaning
RecoveryHow quickly the room clears a particle challenge back to 1% of its starting levelLow air change rate, poor return placement, short-circuiting air
Temperature and humidityConditions across the room against the specified bandsCoil capacity, chilled water temperature, reheat control

ISO 14644-3 does not recommend the recovery test for ISO Class 8 and 9 rooms. The other tests apply to most cleanrooms, with the test state (as built, at rest or operational) agreed beforehand.

The order matters. Airflow and filter integrity come first, because a particle count on an unbalanced room tells you little about why it failed. For how each class limit is calculated, see our guide to ISO 14644-1 cleanroom classification. For the full test scope, see what is cleanroom performance testing.

Common problems found during testing

Most cleanroom HVAC issues are small and fixable once they are measured. The ones that come up most often:

  • Low airflow at terminal filters. Pre-filters load up over time and the room slowly loses air changes. The particle count may still pass at rest and fail in operation.
  • Leaks at filter seals. The filter media is fine, but the gasket or gel seal lets unfiltered air bypass it. A leak scan finds these. A particle count alone often does not.
  • Pressure cascade drift. A new piece of process exhaust or a changed door can flip the flow between two rooms. Nobody notices until the pressure readings are checked against the design.
  • High humidity on hot afternoons. The system holds its band in the morning and drifts after lunch, when the outside air load peaks.
  • Slow recovery. Usually a sign of too little air, or returns placed where supply air short-circuits straight back to the AHU.

For a closer look at the failure causes, read why cleanrooms fail testing. For how airflow is measured in the field, see airflow measurement methods in HVAC.

A cleanroom is only as good as the air system behind it. Testing that system properly, not just counting particles, is how you find out whether it will hold its class on a busy day as well as an empty one.

Frequently asked questions

Is a cleanroom HVAC system the same as a cleanroom ACMV system?
Yes. ACMV (air conditioning and mechanical ventilation) is the term most Malaysian specifications use. HVAC is the more common term internationally.
What filter does a cleanroom HVAC system use?
The final filters are HEPA, or ULPA for the cleanest classes. Upstream, the AHU carries pre-filters and bag filters that protect the HEPAs and extend their life.
How many air changes does a cleanroom need?
ISO 14644 does not fix a number. It depends on the class, the process and the heat load. Rooms at ISO 7 and ISO 8 commonly fall between about 20 and 60 air changes an hour. Unidirectional zones are specified by air velocity instead.
How often should a cleanroom HVAC system be tested?
ISO 14644-2:2015 requires particle count classification at least once a year, and the interval can only be extended where a risk assessment and consistently compliant monitoring data support it. Sterile pharmaceutical rooms under EU GMP Annex 1 are requalified at least every 6 months for Grade A and B, and every 12 months for Grade C and D. Airflow and pressure difference are normally checked on the same cycle, and after any change to the system or the room layout.
Can a cleanroom pass particle count but still have an HVAC problem?
Yes. A room tested at rest can pass with low airflow or a small filter leak, then fail once people and equipment are working. That is why airflow, leak and pressure tests sit alongside the particle count.

Commissioning a new cleanroom, or due for recertification?

Send us your room classes and drawings, and talk through the test scope with a Skud engineer.