TAB · Reading the report

How to read an air balancing report.

An air balancing report is the certified evidence that an air distribution system delivers design airflow within tolerance under the proportional balancing method. This guide reads a TAB report the way a commissioning engineer does: which fields carry the proof, how the ratio column and index terminal are derived, and where a report fails to defend its own numbers.

By Skud Technical· 9 min read· Updated August 2026
The short version
  • A TAB report documents measured against design airflow at every air terminal device, reduced to a ratio (percent of design) under the NEBB proportional balancing method.
  • The certification page, the procedural standard cited, and NIST-traceable instrument calibration are what make the data defensible.
  • Percent of design is the acceptance column, commonly plus or minus 10 percent, with outdoor air and critical exhaust often held to a one-sided band.
  • No identified index terminal, no preliminary readings, or lapsed calibration means the balance cannot be reconstructed or defended.

An air distribution system can be fully installed, energised, and running, and still be out of balance. Fans spin, ductwork is sealed, and yet the branch furthest from the air handling unit starves while the terminals nearest the fan over-deliver. An air balancing report is the document that resolves what the running equipment cannot: whether every terminal delivers design airflow, simultaneously, within tolerance.

It is also the document a consultant or authority signs against at handover. Reading one is therefore an engineering task, not an administrative one. This guide walks the report in the sequence a TAB engineer builds it, so you can see which fields carry the proof and which are decoration.

What is an air balancing report?

An air balancing report, also called a TAB report or HVAC balancing report, presents the measured results of Testing, Adjusting and Balancing carried out to a procedural standard, on critical work the National Environmental Balancing Bureau (NEBB) Procedural Standard for Testing, Adjusting and Balancing of Environmental Systems, and typically worked to ASHRAE Standard 111 and SMACNA methods. It records air quantities at every terminal, static pressure profiles, fan performance at its operating point, and space pressure differentials, each reconciled against design intent.

The objective is singular: to demonstrate, with traceable data, that the installed system performs to the design specification or approved shop drawings. That makes it a controlling document for handover, green building rating submissions such as LEED or GBI, and regulatory compliance in controlled environments.

The six sections of a complete report

Formats vary between providers, but a complete report carries the same six sections. Read them in this order.

1. System overview and readiness

The opening section fixes the scope: project and systems tested, dates, the procedural standard the work was carried out to, and the acceptance tolerances agreed against the specification. A rigorous report also records systems-readiness prerequisites verified before any reading was taken: clean filters installed, access doors and inspection panels sealed, volume control dampers set to a full-open datum, terminals unobstructed, and controls in a defined state. TAB carried out on a system that was not ready produces numbers that cannot be repeated. The section should also state the NEBB certification held by the professionals signing the report (Certified Professional or Certified Technician).

2. Air terminal device (ATD) readings and the proportional method

This is the core of the report: a schedule, terminal by terminal, of design airflow against measured airflow, reduced to a ratio. Under the proportional balancing method, terminals on a branch are set to a common ratio of measured to design before the total is trimmed at the fan. The terminal with the least favourable ratio, the index (reference) terminal, keeps its volume control damper fully open, and every other terminal is throttled to match its ratio. Only then is the fan set to deliver total design airflow. Reading the report, the ratio column is where you judge acceptance, and the identified index terminal is your evidence that the branch was proportioned rather than each outlet fiddled in isolation.

Air terminal device schedule, worked example
Location / deviceDesignMeasuredRatioResult
Ward A · Diffuser D-012502460.98Pass
Ward A · Diffuser D-022502380.95Pass
Ward A · Diffuser D-03 index1801510.84Below
Corridor · Grille R-043203311.03Pass
Airflow in litres per second (L/s) for illustration; ratio is measured divided by design. D-03 is the index terminal (lowest ratio, damper full open). At 0.84 it sits outside a plus or minus 10 percent tolerance, which means the branch cannot be proportioned up to design without addressing fan capacity or duct leakage upstream.

Read the ratio column first, not the raw airflow. A terminal at 1.03 is within tolerance. The index terminal at 0.84, damper already fully open, is the diagnostic case: if the least-favourable terminal cannot reach design with no further damper authority available, the shortfall is upstream (fan operating point, system effect, or duct leakage), not a balancing problem at the outlet. Watch also for terminals whose measured quantities sum beyond the fan’s measured airflow, an arithmetic impossibility that points to uncompensated hood readings or fabricated data.

3. Room pressurization and air offset

For hospitals, laboratories, and cleanrooms, differential pressure is a performance requirement, not a by-product. This section reports the pressure cascade between spaces, driven by the air offset (supply minus return and exhaust) engineered into each room. A room that cannot hold its design differential loses directional airflow control, which in a controlled space means contamination risk and a compliance failure.

Space pressurization, worked example
SpaceReferenceDesign ΔPActual ΔPResult
Isolation roomCorridor−15 Pa−16 PaPass
Clean corridorAirlock+10 Pa+11 PaPass
PreparationCorridor+8 Pa+3 PaLow
Differential pressure in pascals (Pa) for illustration. Preparation holds only +3 Pa against a +8 Pa design offset, insufficient to maintain the intended cascade, and is flagged for offset re-adjustment and envelope leakage check.

Space pressurization, along with air change rate, sits alongside particle count and recovery within cleanroom performance testing, a related but separate certified scope.

4. Equipment summary and fan operating point

Terminal readings tell you where the air landed. The equipment sheets tell you whether the source can sustain it. For each air handling unit and fan, the report records total airflow, external static pressure, fan speed or VFD frequency, motor nameplate full-load amps against measured running amperage, and coil entering and leaving conditions with the resulting temperature differential. Together these locate the fan on its curve. The fan laws govern any speed change made to reach design: airflow varies with speed, static pressure with the square of speed, and absorbed power with the cube, so a modest airflow correction can carry a large power and static penalty. A fan driven well past its design operating point to force terminals to design, or one showing running amps near nameplate, is a finding in itself, even when the terminals read within tolerance.

5. Instrument list and calibration data

Before trusting any reading, find this section. A defensible report names each instrument, the capture hood, micromanometer, rotating-vane and thermal anemometers, tachometer, and clamp ammeter, with serial numbers and current NIST-traceable calibration certificates. Measurement method matters here: hood readings should be back-pressure compensated, face-velocity traverses applied with the manufacturer’s effective area (Ak) factor, and ducted airflow taken by a Pitot velocity-pressure traverse with points set by the log-Tchebycheff rule. An instrument outside its calibration interval produces confident numbers that are quietly wrong, and calibration dates that lapsed before the site visit invalidate every figure downstream.

▸ A report is a chain of trust: certification, then traceable instruments, then the ratio column. A break anywhere upstream invalidates everything below it.

6. Observations and deficiencies

The most useful page in a rigorous report is the one that records what is not yet within tolerance: terminals outside the acceptance band, index terminals fully open yet below design (an upstream capacity or leakage indication), spaces off their pressure offset, fans operating off-curve, and suspected duct leakage against the specified leakage class. Each item should carry a defined corrective action. Counterintuitively, a report with an honest deficiency log is more trustworthy than one reporting a perfect first pass. Real systems have exceptions; a report showing none has usually not measured hard enough to find them.

How to spot a weak report in under a minute
  • No signed certification statement, and no procedural standard cited.
  • No index terminal identified, so proportional balancing cannot be verified.
  • Final readings only, with no preliminary data, so the balance cannot be reconstructed.
  • Instrument calibration absent, or NIST-traceable dates lapsed before the site work.
  • Terminal quantities that sum beyond the fan’s measured airflow, which is arithmetically impossible.
  • Acceptance tolerance never stated, so pass and fail have no definition.

Air balancing is not commissioning

Commissioning is the broad process of proving a whole building system performs across controls, sequences, and integration. Air balancing is the specialist measurement discipline inside it: driving air quantities to design and documenting the proof to a procedural standard. A commissioning manager depends on the balancing report as source evidence, but the two are distinct deliverables produced under different scopes. When scoping a project it helps to see where commissioning management and testing, adjusting and balancing each begin and end.

What a defensible report should contain

Skud Technical is Malaysia’s only firm certified by the National Environmental Balancing Bureau (NEBB) in both TAB and Cleanroom Performance Testing, and every report is built to be read, audited, and signed. A report that holds up at handover includes:

  • A design against measured comparison with a ratio column for every air terminal device, and the index terminal identified on each branch.
  • Preliminary and final readings, so the proportional balance can be reconstructed, not just its result asserted.
  • Instrument serial numbers with current NIST-traceable calibration certificates behind every figure.
  • A signed certification statement, worked to the NEBB procedural standard and signed by NEBB-certified professionals.
  • A deficiency log with defined corrective actions, and a format built for consultant and authority sign-off aligned to the commissioning plan.

Read this way, the report becomes what it is meant to be: a traceable, defensible record that the air distribution system performs to design, ready for sign-off, with no question the document has not already answered.

Frequently asked questions

What tolerance does NEBB apply to air balancing?
Air terminal quantities are commonly accepted within plus or minus 10 percent of design, but the governing figure is the project specification, not a default. Many specifications tighten this: outdoor air and critical exhaust are often held to a one-sided band such as zero to plus 10 percent, so a space is never starved of ventilation or under-extracted. A credible report states the tolerance every reading was judged against.
What is the proportional balancing method?
Proportional balancing sets every terminal on a branch to the same ratio of measured to design airflow before the total is trimmed at the fan. The terminal with the lowest ratio, the index terminal, keeps its volume control damper fully open, and the others are throttled to match it. This avoids the error of balancing terminals in isolation, where adjusting one outlet throws out the next.
What is the index terminal in a TAB report?
The index or reference terminal is the outlet on a branch with the least favourable ratio of measured to design airflow. Under the proportional method its damper stays fully open and the rest of the branch is balanced to it. A report should identify it, because it is the evidence that proportional balancing was actually performed rather than terminals being set individually.
What instruments measure airflow at a diffuser?
A capture hood reads terminal airflow directly and should be back-pressure compensated. Where a hood does not fit, a rotating-vane or thermal anemometer traverse across the face is used with the manufacturer’s effective area (Ak) factor to convert velocity to airflow. Ducted airflow is measured by a Pitot velocity-pressure traverse with points distributed by the log-Tchebycheff rule. Every instrument carries NIST-traceable calibration.